WIRE SIZE | CONSTANT METHOD | WIRE AMPERAGE RATING | 80% AMPERAGE CAPACITY | 12 VOLTS | MAX WATTAGE | RECOMMENDED WIRE WATTAGE LOAD | |||||
18/2 | 1380 | 6 | 4.8 | 12 | 57.6 | 43.2 | |||||
16/2 | 2200 | 10 | 8 | 12 | 96 | 72 | |||||
14/2 | 3500 | 15 | 12 | 12 | 144 | 108 | |||||
12/2 | 7500 | 20 | 16 | 12 | 192 | 144 | |||||
10/2 | 11920 | 30 | 24 | 12 | 288 | 216 | |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | |
LOCATION | RUN LENGTH | WATTS | TOTAL | X 2 | TOTAL | DIVIDE WIRE SIZE CONSTANT METHOD | SUM OF VOLTAGE DROP | TAP NEEDED | COLOR | CONNECTION STATUS | RUN AMPERAGE |
TRANSFORMER | |||||||||||
*FINDING THE TAP TO USE ON YOUR TRANSFORMER
|
|||||||||||
1. ENTER NAME LOCATION (Group fixtures within a reasonable proximity of each other and name their location)
|
|||||||||||
2. ENTER RUN LENGTH (Measure the run length from the farthest fixture to the transformer)
|
|||||||||||
3. ENTER TOTAL WATTAGE (Add all bulb wattage on that run. Be sure not to exceed the recommended wattage on the run)
|
|||||||||||
4. ENTER SUM OF LINE 2 X LINE 3 (Multiply the run length by the total wattage)
|
|||||||||||
5. ENTER THE SUM OF LINE 4 X 2 (Multiply the sum of line 3 times by 2)
|
|||||||||||
6. SELECT THE WIRE SIZE CONSTANT
|
|||||||||||
7. ENTER THE SUM OF LINE 5 DIVIDED BT LINE 6
|
|||||||||||
8. ADD THE SUM OF LINE 7 TO 12
|
|||||||||||
9. WRAP A DIFFERENT COLOR TAPE AROUND THE WIRE AT THE TRANSFORMER TO IDENTIFY THE RUN AND ENTER
|
|||||||||||
10. DOCUMENT STATUS OF CONNECTION
|
|||||||||||
11. DOCUMENT RUN AMPERAGE
|